MB-350U | MB-350U-V | |
---|---|---|
Sensing Method | CO₂- NDIR (Non-dispersive Infrared) Single Type Humidity, Temperature | CO₂- NDIR (Non-dispersive Infrared) Single Type VOCs- Semiconductor Type Humidity, Temperature |
Dimensions | 135mm x 90mm x 28mm (W*H*D) | |
CO₂ Measurement range | 0 to 10,000 ppm | |
Accuracy |
CO2 : 30ppm ± 3% of Reading Temperature : ± 0.3 ℃ typical (-40℃ ~ 80℃) Humidity : ± 2% RH typical (0~ 99% RH) |
|
Operating Temperature range | 0℃ to 50℃ | |
Storage Temperature | -30℃ to 70℃ | |
Operating Humidity range | 0 to 95% RH (Non-condensing) | |
Input Power | DC 12V/1A AC/DC adaptor | |
CO₂Step Response Time(90%) | 150 sec | |
CO₂ Sampling Interval | 3 sec | |
CO₂ Output | LCD display, LED display (Very high / High / Normal), Alarm=> Melody warning USB output | LCD display , Alarm => Melody warning, USB output |
VOCs Output | without VOC | Very high / High / Normal LED indicate |
CO Output | without CO | without CO |
Product | Option | |||||
---|---|---|---|---|---|---|
USB | CO2 | Temp.+ Humid. | VOCs | RS-485 | CO | |
MB-350 | X | ● | ● | X | X | X |
MB-350V | X | ● | ● | ● | X | X |
MB-350U | ● | ● | ● | X | X | X |
MB-350U-V | ● | ● | ● | ● | X | X |
MB-350U-485 | ● | ● | ● | X | ● | X |
MB-350U-V485 | ● | ● | ● | ● | ● | X |